2. Pre-Installation

2.3

Enclosure Grounding

Lightning Protection (Optional)

1/2" x 8' copper ground rod, four places, driven about 2 feet (typical) from the corners of the pad.

#2 bare copper wire loop terminated to each ground rod and buried below grade 2 to 12 inches.
Corrosion-proof connections (25+ year life-span) and hardware suitable for direct burial MUST be used

#2 bare copper wire from loop to the enclosure

When the electrical supply is a primary service (not a secondary or feeder service) a #2 bare copper wire
must be bond the lightning protection loop to the Grounding Electrode Conductor where they are closest.

Service Grounding (required)

#6 bare copper wire from Service Neutral / Ground Bar with 2 ground rods located 6' apart.