Figure 2-4; alternate grounding, pn-3 and pn-4, Pre-installation, Continued – Alpha Technologies PN-4 User Manual

Page 14: 3 enclosure grounding

Advertising
background image

2. Pre-Installation

14

031-103-B0-003 Rev. C

© 2002

TM

2.3

Enclosure Grounding,

continued

Lightning Protection (Optional)

1/2" x 8' copper ground rod, four places, driven about 2 feet (typical) from the corners of the pad.

#2 bare copper wire loop terminated to each ground rod and buried below grade 2 to 12 inches.
Corrosion-proof connections (25+ year life-span) and hardware suitable for direct burial MUST be used.

#2 bare copper wire from loop to the enclosure

When the electrical supply is a primary service (not a secondary or feeder service) a #2 bare copper wire
must be bonded to the lightning protection loop to the Grounding Electrode Conductor where they are
closest.

Service Grounding (required)

#2 bare copper wire from Service Neutral / Ground Bar down 30 inches and out 20 feet beyond the pad
edge. This is often called a UFER ground (Ground Ring in the NEC).

Opening for

Sweeps

Opening for

Sweeps

Enclosure Footprint

20 feet (minimum)

2 f

ee

t

(m

in)

8

211(&7,21

Г

0$'(

Г

:,7+

7

851'<

Ã

&211(&725



3



1

Ã`BCS$'8!X"Ã

25

(48,9$/(17



8

211(&7,21

Г

0$'(

Г

:,7+

7

851'<

Ã

&211(&725



3



1

Ã`BCQ$'8!X!UI

25

Ã

(48,9$/(17



30
i

n

c

hes

Side view

UFER Ground

SE

conduit &

wires

GEC

#2 bare
copper

wire

No

separation

is required.

#2 AWG

#2 AWG

Opening for

Sweeps

1

2

3

4

5

4

5

1

2

3

Figure 2-4; Alternate Grounding, PN-3 and PN-4