Warning, Caution – AAON M3-094 User Manual

Page 10

Advertising
background image

10




























































































Some

chemical

coil

cleaning

compounds are caustic or toxic. Use
these substances only in accordance
with

the

manufacturer

’s

usage

instructions.

Failure

to

follow

instructions may result in equipment
damage, injury or death.

WARNING


Door

compartments

containing

hazardous voltage or rotating parts
are equipped with door latches to
allow locks. Door latch are shipped
with nut and bolts requiring tooled
access. If you do not replace the
shipping hardware with a pad lock
always re-install the nut & bolt after
closing the door.

CAUTION


Check the shipping section weights
on the Bill of Lading to be sure they
can be lifted safely. Rigging should
be adjusted so that all sections are
lifted level.

WARNING


Do not enter or reach into a fan
cabinet while the fan is still turning.

WARNING


Never attempt to open an access
door or remove a panel while the unit
is running. Pressure in the unit can
cause excessive force against the
panel.

WARNING


Never pressurize equipment over 8”
w.c

– Equipment and property

damage, personal injury or loss of life
could result.

WARNING


Ensure that sufficient dampers will be
open to provide air path before fan is
allowed to run.

WARNING


Risk of injury from hot parts

Disconnect all power, close all
isolation valves and allow equipment
to cool before servicing equipment
with hot water and steam heating
coils. Hot water will circulated even
after the power is off.

WARNING


PVC (Polyvinyl Chloride) and CPVC
(Chlorinated Polyvinyl Chloride) are
vulnerable to attack by certain
chemicals. Polyolester (POE) oils
used

with

R-410A

and

other

refrigerants, even in trace amounts,
in a PVC or CPVC piping system will
result in stress cracking of the piping
and fittings and complete piping
system failure.

CAUTION

Advertising
This manual is related to the following products: