Electrical, Foam insulated panel cutting, Figure 29 - external control panel – AAON M3-094 User Manual

Page 55: Caution, Warning

Advertising
background image

55

Figure 29 - External Control Panel








Electrical
All external wiring must comply with the
National Electric Code (NEC) and any
additional local codes. It is the responsibility
of the installer to conform to all necessary
codes. All internal wiring complies with UL
1995

Note: All voltages should be within 10% of
unit and component nameplate voltages.

Check the unit data plate to make sure it
agrees with the power supply. For units
that contain factory wiring, connect power
supply to the unit according to the provided
wiring diagram.

All wiring should be done in conduit on the
exterior of the unit. Control wiring should

not be run in the same conduit as power
wiring. Protect the branch circuit in
accordance with code requirements.

The unit must be electrically grounded in
accordance with the National Electric Code,
ANSI / NFPA No. 70. In Canada use current
C.S.A. Standard C22.1, Canadian Electric
Code Part 1.

For field wired units, refer to the motor
connection diagram on the inside of the
motor terminal box for wiring instructions.
Check the electrical characteristics of the
motor to make sure they correspond to the
supply voltage and the conductor size used.










Foam Insulated Panel Cutting










Note: The location for field cut electrical
entry is marked on the unit. Field cut
openings must be a minimum of 6 inches
away from all components and wiring to
prevent damage due to drilling or cutting.

To pass wires through the wall or roof of the
unit, a hole should be cut and conduit passed


Anytime a foam insulated part has a
hole or cutout in it, the exposed foam
must be sealed from the air stream.

CAUTION


All high voltage electrical connections
should be checked for tightness prior
to unit startup. Loose connections
can

cause

overheating

and

component failure.

CAUTION


The

foam

insulation

releases

dangerous fumes when it is burnt. Do
not cut a foam part with a cutting
torch or plasma cutter. Do not weld to
a foam filled part.

WARNING

Advertising
This manual is related to the following products: