1. Startup and service must be performed

by

a

Factory

Trained

Service

Technician.


2. The unit is for outdoor use only. See

General Information section for more
information.


3. Use only with type of the gas approved

for the boiler. Refer to the boiler rating
plate.

4. Provide adequate combustion ventilation

air to the boiler.

5. Every unit has a unique equipment

nameplate with electrical, operational,
and

unit

clearance

specifications.

Always refer to the unit nameplate for
specific ratings unique to the model you
have purchased.


6. READ THE ENTIRE INSTALLATION,

OPERATION AND MAINTENANCE
MANUAL.

OTHER

IMPORTANT

SAFETY

PRECAUTIONS

ARE

PROVIDED THROUGHOUT THIS
MANUAL.

7. Keep this manual and all literature

safeguarded near or on the unit.


Some

chemical

coil

cleaning

compounds are caustic or toxic. Use
these substances only in accordance
with

the

manufacturer

’s

usage

instructions.

Failure

to

follow

instructions may result in equipment
damage, injury or death.

WARNING


Do not clean DX refrigerant coils with
hot water or steam. The use of hot
water or steam on refrigerant coils
will cause high pressure inside the
coil tubing and damage to the coil.

CAUTION


Door

compartments

containing

hazardous voltage or rotating parts
are equipped with door latches to
allow locks. Door latch are shipped
with nut and bolts requiring tooled
access. If you do not replace the
shipping hardware with a pad lock
always re-install the nut & bolt after
closing the door.

CAUTION


Polyolester (POE) and Polyvinylether
(PVE) oils are two types of lubricants
used in hydrofluorocarbon (HFC)
refrigeration systems. Refer to the
compressor label for the proper
compressor lubricant type.

CAUTION


COMPRESSOR CYCLING

5 MINUTE MINIMUM OFF TIME

To

prevent

motor

overheating

compressors must cycle off for a
minimum of 5 minutes.

5 MINUTE MINIMUM ON TIME

To maintain the proper oil level
compressors must cycle on for a
minimum of 5 minutes.

The cycle rate must not exceed 6
starts per hour.


WARNING