Gas connection, Boiler exhaust connection, Warning – AAON LL-540 User Manual

Page 29: Caution

Advertising
background image

29
















Gas Connection
For LL Series outdoor mechanical units with
boiler systems, size gas piping to supply the
unit with proper pressure when all gas
consuming

devices

in

the

building

connected to the same gas system are
operating. The maximum gas train inlet
pressure for all boiler sizes is 5 psig. The
minimum gas train inlet pressure for the 500
MBH boiler is 5 inches of water column,
and for all other boilers, 7 inches of water
column.

Carefully consider all current and future gas
usage. Table 3 details the input rate for each
boiler unit.

Gas connection sizes are listed on the unit
rating sheet.

Table 3 - Boiler Rated Input Capacity

Boiler Size

Rated Capacity (CFH)*

Natural

LP/Propane

500 MBH

500

200

750 MBH

750

300

1000 MBH

1000

400

1500 MBH

1500

600

*Note: Rating is for sea level conditions.

For additional information regarding the gas
piping

connection,

see

the

Thermal

Solutions Boiler “Installation, Operating,
and Service Instructions” that are included
with the unit.

Boiler Exhaust Connection
In addition to gas connection installation,
each boiler requires installation of the
exhaust vent piping and inlet vent hood. The
exhaust panel with chimney cutout is
removed for shipping, and replaced with a
shipping cover.

Figure 7 - Boiler Vent Shipping Covers


Remove the shipping cover and attach the
exhaust panel shipped with the unit. When
the exhaust panel is securely fastened with


Boilers must be operated only with
liquid flowing through the boiler.

WARNING


Installing Contractor is responsible
for proper sealing of the water piping
entries into the unit Failure to seal the
entries may result in damage to the
unit and property.

CAUTION

Advertising