Water/Glycol System

1. Has the entire system been flushed and pressure checked?

Yes No

2. Have isolation valves to the chiller been installed?

Yes No

3. Have isolation valves to the boiler been installed?

Yes No

4. Has the entire system been filled with fluid?

Yes No

5. Has air been bled from the heat exchangers and piping?

Yes No

6. Is there a minimum load of 50% of the design load?

Yes No

7. Has the water piping been insulated?

Yes No

8. Is the glycol the proper type and concentration (N/A if water)?

Yes No

9. What is the freeze point of the glycol (N/A if water)? ______________________________


Chiller Configuration

Air-Cooled Condenser

Evaporative-Cooled Condenser

Low Ambient Control

Condenser Safety Check

No Water Leaks

Water Flow ________ gpm

Chilled Water In Temperature ________°F

Chilled Water Out Temperature ________°F


Boiler Configuration

No Water Leaks

Boiler Water Flow ________ gpm

Boiler Safety Check

Boiler Building Water Flow ________ gpm