Caution – AAON LL-540 User Manual

Page 43

Advertising
background image

43

system with an expansion valve liquid sub-
cooling is more representative of the charge
than

evaporator

superheat

but

both

measurements must be taken.























Before Charging
Refer to the unit nameplate as a reference
when determining the proper refrigerant
charge.

Unit being charged must be at or near full
load conditions before adjusting the charge.

Units equipped with hot gas bypass must
have the hot gas bypass valve closed to get
the proper charge.

After adding or removing charge the system
must be allowed to stabilize, typically 10-15
minutes,

before

making

any

other

adjustments.

The type of unit and options determine the
ranges for liquid sub-cooling and evaporator

superheat.

Refer

to

Table

9

when

determining the proper sub-cooling.

For units equipped with low ambient (0°F)
option see the special charging instructions
at the end of this section.

Checking Liquid Sub-cooling
Measure the temperature of the liquid line as
it leaves the condenser coil.

Read the gauge pressure at the liquid line
close to the point where the temperature was
taken. You must use liquid line pressure as it
will vary from discharge pressure due to
condenser coil pressure drop.
Convert the pressure obtained to a saturated
temperature using the appropriate refrigerant
temperature-pressure chart.

Subtract

the

measured

liquid

line

temperature from the saturated temperature
to determine the liquid sub-cooling.

Compare calculated sub-cooling to the table
below for the appropriate unit type and
options.

Checking Evaporator Superheat
Measure the temperature of the suction line
close to the compressor.

Read gauge pressure at the suction line close
to the compressor.

Convert the pressure obtained to a saturated
temperature using the appropriate refrigerant
temperature-pressure chart.

Subtract the saturated temperature from the
measured suction line temperature to
determine the evaporator superheat.

For refrigeration systems with tandem scroll
compressors, it is critical that the suction
superheat setpoint on the expansion valve is


The Clean Air Act of 1990 bans the
intentional venting of refrigerant
(CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery,
recycling or reclaiming must be
followed. Fines and/or incarceration
may be levied for non-compliance.

CAUTION


Polyolester (POE) and Polyvinylether
(PVE) oils are two types of lubricants
used in hydrofluorocarbon (HFC)
refrigeration systems. Refer to the
compressor label for the proper
compressor lubricant type.

CAUTION

Advertising