5. Determine whether the pin is in the HUB

or RET

Figure 19 - Fan HUB and RET Castings



6. Determine the current blade pitch and the pin location for the new blades

Table 5 - Return/Exhaust Fan Pin Location

Type

Bushing

Mount

Blade Pitch Angle

20°

25°

28°

30°

33°

35°

38°

40°

45°

50°

5Z

A

-

RET

-

RET

RET

RET

HUB

HUB

HUB

HUB

B

-

HUB

-

HUB

HUB

HUB

RET

RET

RET

RET

Table 6 - Return/Exhaust Fan Pin Location

Type

Rot.

Blade Pitch Angle

20°

25°

28°

30°

33°

35°

38°

40°

45°

50°

5Z

R

-

4

-

3

2

1

4

3

2

1

L

-

1

-

2

3

4

1

2

3

4