45

in

the

summer

when

the

ambient

temperature is cold:

Once enough charge has been added to get
the evaporator superheat and sub-cooling
values to the correct setting more charge
may need to be added. If the ambient
temperature is 0°F no more charge is
required. If the ambient temperature is
around 40°F add approximately 40% of the
receiver tank volume.

The unit will have to be checked for proper
operation once the ambient temperature is
above 80°F.










Table 10 - R-134a Refrigerant Temperature-Pressure Chart

°F

PSIG

°F

PSIG

°F

PSIG

14

15

63

61

111

149

16

16

64

63

113

154

18

17

66

66

115

158

19

18

68

68

117

163

21

19

70

71

118

167

23

21

72

74

120

172

25

22

73

76

122

177

27

24

75

79

124

181

28

25

77

82

126

186

30

26

79

85

127

191

32

28

81

88

129

197

34

30

82

91

131

202

36

31

84

94

133

207

37

33

86

97

135

213

39

34

88

100

136

218

41

36

90

104

138

224

43

38

91

107

140

229

45

40

93

111

142

235

46

42

95

114

144

241

48

44

97

118

145

247

50

46

99

121

147

253

52

48

100

125

149

260

54

50

102

129

151

266

55

52

104

133

153

272

57

54

106

137

154

279

59

56

108

141

156

286

61

59

109

145

158

293


DO NOT OVERCHARGE!


Refrigerant overcharging leads to
excess refrigerant in the condenser
coils resulting in elevated compressor
discharge pressure.

CAUTION