Code Faults

Cause
of the
fault

Description

Checking / solution

L14

BURNER FAILURE

PCU

5 burner start-up failures

No ignition

4

Contact the professional who takes care of

maintenance of the appliance

Ignition arc, but no flame formation

4

Check that the gas valve is fully opened

4

Contact the professional who takes care of

maintenance of the appliance

Presence of the flame but insufficient ionization

(<3 µA)

4

Check that the gas valve is fully opened

4

Contact the professional who takes care of

maintenance of the appliance

L16

PARASIT FLAME

PCU

Detection of a parasite flame

Ionization current present even though there is no

flame

Ignition transformer defective

Gas valve defect

The burner remains very hot: CO

2

too high

4

Contact the professional who takes care of

maintenance of the appliance

L17

VALVE FAIL

PCU

Problem on the gas valve

SU PCB faulty

4

Contact the professional who takes care of

maintenance of the appliance

L34

FAN FAILURE

PCU

The fan is not running at the right

speed

Bad connection

Fan defective

4

Contact the professional who takes care of

maintenance of the appliance

L35

BACK>BOIL FAIL

PCU

Flow and return reversed

Bad connection

Sensor fault

4

Contact the professional who takes care of

maintenance of the appliance

Water circulation direction reversed

4

Check the circulation (direction, pump,

valves)

L36

I-CURRENT FAIL

PCU

The flame went out more than 5

times in 24 hours while the burner

was operating

No ionization current

4

Check that the gas valve is fully opened

4

Contact the professional who takes care of

maintenance of the appliance

L37

SU COM.FAIL

PCU

Communication failure with the SU

PCB

Bad connection

4

Contact the professional who takes care of

maintenance of the appliance

L38

PCU COM.FAIL

PCU

Communication failure between the

PCU and SCU PCBs

Bad connection

SCU PCB not connected or faulty

4

Contact the professional who takes care of

maintenance of the appliance

L39

BL OPEN FAIL

PCU

The BL inlet opened for a short time Bad connection

External cause

Parameter incorrectly set

4

Contact the professional who takes care of

maintenance of the appliance

6. Troubleshooting

AGC 10/15 AGC 15 AGC 25 AGC 35

33