13 fluid connection – Burkert Type 8793 User Manual

Page 26

Advertising
background image

26

Fluid connection

Type 8792, 8793

→

Attach remote sensor on the actuator.
The correct procedure is described in the instructions for the
path sensor.

→

Connect compressed air to the Type 8793.

→

Connect Type 8793 pneumatically to the actuator

→

Switch on Type 8793 operating voltage.

→

To obtain the best possible control precision, adjust the path
sensor so that path to be measured corresponds to the signal
range 4 – 20 mA (only if the path sensor includes this function).

→

In the

ADD.FUNCTION menu activate the POS.SENSOR

function. Then select

POS.SENSOR in the main menu and set

ANALOG.
The procedure is described in the operating instructions for Type
8792/8793 in the chapter

“Starting up and operation of the

process controller / auxiliary functions / POS.SENSOR”.

→

Run the

X.TUNE function.

13 FLUID CONNECTION

DANGER!

Risk of injury from high pressure in the equipment!

▶ Before loosening the pneumatic lines and valves, turn off the

pressure and vent the pneumatic lines.

WARNING!

Risk of injury from improper installation!

▶ Installation may be carried out by authorized technicians only

and with the appropriate tools!

Risk of injury from unintentional activation of the system and
an uncontrolled restart!

▶ Secure system from unintentional activation.

▶ Following installation, ensure a controlled restart.

Working connection 2
(connection: A2)

Supply pressure connection
1.4 – 7 bar (connection: P)

Working connection 1 <
(connection: A1)

Deaeration connection

Fig. 16: Fluid installation / Location of the connections