36

Electrical Installation

Type 8792, 8793

Connection of a potentiometric position sensor:

Terminal Configuration

On the
device
side

External circuit

Potentiometer 1 1

Potentio-
meter

Center tap 2

2

Center tap

Potentiometer 3 3

Tab. 16: Terminal assignment; potentiometric position sensor

When the operating voltage is applied, the positioner is operating.

→

Now make the required basic settings and actuate the automatic
adjustment of the positioner. The procedure is described in chapter
“16.2 Starting-up Type 8792”

14.7 Terminal assignment for cable

gland - process controller Type
8793

→

First connect the process controller as described in chapter
“14.6 Terminal assignment for cable gland - positioner Type
8792”
.

14.7.1 Terminal assignments of the process

actual value input

Input
type*

Terminal Configuration

On the
device side

External
circuit

4 ... 20 mA
- internally
supplied

actual value

1

+24 V Input
transmitter

1

2

3

GND

Trans-
mitter

GND

2

Output from
transmitter

3

Bridge to GND
(Terminal GMD from
operating voltage)

4

not used

GND

GND from operating
voltage

4 ... 20 mA
- externally
supplied

actual value

1

not used

2

Process actual +

2

+ (4...20 mA)

3

Process actual –

3

GND

4

not used

english