Electrical Installation

Type 8792, 8793

Input
type*

Terminal Configuration

On the
device side

External
circuit

Frequency
-internally
supplied

actual value

1

+24 V sensor supply

1

+24 V

2

Clock input +

2

Clock +

3

not used

4

Clock input –

4

GND

GND from operating
voltage

GND

Clock
– (GND)

Frequency
- externally
supplied

actual value

1

not used

2

Clock input +

2

Clock +

3

not used

4

Clock input –

4

Clock –

Pt 100
see infor-
mation**

actual value

1

not used

2

3
4

Pt 100

2

Process actual 1
(Power supply)

3

Process actual 3
(GND)

4

Process actual 2
(Compensation)

*

Can be adjusted via software

(see Operating Instructions,chapter „Specifying the standard settings“)..

Tab. 17: Terminal assignments of the process actual value input

** Connect the Pt 100 sensor via 3 cables for cable com-

pensation reasons.
It is essential to bridge Pin 3 and Pin 4 on the sensor.

When the operating voltage is applied, the process controller is
operating.

→

Now make the required basic settings and actuate the automatic
adjustment of the process controller. The procedure is described
in chapter “16.3 Start-up Type 8793”.