INstallation

1 2 3 4 5 6

4...20 V+ V- PE Pls+ Pls-

C

NO
NC

B

A

2

1

3

selector

A

: Sink/source

selector of the 4-20 mA
output

terminal block 3

Terminal 1: 4-20 mA output

Terminal 2: V+ (positive
voltage)

Terminal 3: V- (power supply
ground)

Terminal 4: PE, shield of
the power supply cable;
Earth cable coming from the
housing and, second cable
on a version with flow sensor
holder in stainless steel (see
Fig. 15)

Terminal 5: Pls+, positive
frequency output

Terminal 6: Pls-, negative
frequency output

connector 1: connection of the
flat cable coming from the flow
sensor (to energize the flow
sensor)

terminal block 2: wiring the
relay output

C: common point

NO: normally open

NC: normally closed

leD

B

: status LED of the relay

(LED ON = contact closed)

Fig. 14: Terminal assignment

make sure the installation is equipotential (power supply
- 8041):

→

Connect together the various earth spots in the instal-
lation to eliminate the potential differences that may occur
between two earthes.

→

In the housing, connect the power supply cable shield to
terminal no. 4 of the electronic board connector (Fig. 15).
On a version with stainless steel flow sensor, a second
cable is coming from the sensor.

→

Connect the negative power supply terminal to the earth
to suppress the effects of common mode currents. If
this connection cannot be made directly, a 100 nF/50 V
capacitor can be connectec between the negative power
supply terminal and the earth (marked 1, Fig. 16).

• If the pipes are made of metal:

→

connect to the same earth the different metallic instru-
ments (valve, pump...) located near the device (marks 2,
Fig. 16).

• If the pipes are made of plastic:

→

insert the metal parts (not provided) in the plastic pipes,
upstream and downstream of the device (marked 2, Fig.
16).

→

connect the metal parts to the same earth (Fig. 16).