Burkert Type 8041 User Manual

Page 54

Advertising
background image

52

Maintenanceandtroubleshooting

problem

bargraph
state

red leD state

Green leD
state

current or
frequency
output
state

meaning / cause

recommended action

The flow rate
measure-
ments are not
stable

Unstable

OFF

Flashes once
every second

> 4 mA
and
> 0 Hz

The electrodes are dirty.

→

Clean the electrodes (see chap.
10.3).

The electrodes are not in
contact with the fluid.

→

Make sure the electrodes are always
in contact with the fluid

Air bubbles appear in the
fluid.

→

Respect the mounting recommenda-
tions (see chap. 8.2).

→

Select the "slow" filter (see chap.
9.5).

The flow sensor has not
been immersed for 24 h
before calibration of the
"flow zero" point.

→

Respect the calibration procedure
(see chap. 9.7).

The flow rate fluctuations
are very important.

→

Select the "slow" filter (see chap.
9.5).

Upstream-downstream
connection has not been
correctly done.

→

Respect the mounting recommenda-
tions (see chap.

8.2).

The device
transmits no
current or no
frequency at
all.

shows a
value

OFF

Flashes once
every second

0 mA and/or
0 Hz

The position of the sink/
source selector is not
correct.

→

Correctly position the sink/source
selector (see chap. 8.3.1).

The outputs are not cor-
rectly wired.

→

Check the wiring of the outputs (see
chap. 8.3.1, 8.3.2, 8.3.3).

The sensor
does not
measure a nil
flow rate.

Lit

OFF

Flashes once
every second

> 4 mA and
> 0 Hz

The calibration of the flow
zero point has not been
correctly done.

→

Calibrate again (see chap. 9.7).