FLUID COMPONENTS INTERNATIONAL LLC

ST51 MASS FLOW

This page is subject to proprietary rights statement on last page

2

Doc. No. 06EN003389 Rev. -

Instrument

Media Compatibility: Biogas, Digester Gas, Methane, Natural

Gas, Air, Compressed Air, Nitrogen

Pipe/Line Size Compatibility: 2" to 24" [51 mm to 610 mm]

Flow Range: 0.3 sfps to 400 sfps [0,08 mps to 122 mps]

Accuracy: (at >0.75 sfps [>0,21 nmps] )

Standard: ± 2% reading ± 0.5% full scale

Optional: ± 1% reading ± 0.5% full scale

Repeatability: ± 0.5% reading

Temperature Compensation:

Standard: 40 °F to 100 °F [4 °C to 38 °C]

Optional: 0 °F to 250 °F [-18 °C to 121 °C]

Turndown Ratio: 3:1 to 100:1

Agency Approvals:

ATEX/IEC Ex: II 2 G Ex d IIC T6...T3

II 2 D Ex tD A21 IP67 T90°C...T121°C

FM, CSA:

Class I, Div. 1, Groups B, C, D (Enclosure only)

Class I, Div. 2 Pending

CRN No.:

0F0303

Warranty: 1 year

Flow Element

Installation: Insertion, variable length with 1/2" or 3/4" NPT(M)

compression fitting.

Type: Thermal Dispersion

Material of Construction: 316L stainless steel body with

Hastelloy-C22 thermowell sensors, 316 stainless steel

compression fitting with Teflon or stainless steel ferrule.

Pressure (Maximum Operating without Damage):

Stainless steel ferrule: 500 psig [34 bar(g)]

Teflon ferrule: 150 psig [10 bar(g)]

Operating Temperature:

Stainless steel ferrule: 0 °F to 250 °F [-18 °C to 121 °C]

Teflon ferrule: 0 °F to 200 °F [-18 °C to 93 °C]

Process Connection: 1/2" MNPT or 3/4" MNPT with stainless

steel or Teflon ferrule.

Insertion Length (Field Adjustable):

1" to 6" [25 mm to 152 mm]

1" to 12" [25 mm to 305 mm]

1" to 18" [25 mm to 457 mm]

Flow Transmitter

Enclosure: NEMA 4X [IP67], aluminum, dual conduit

ports with either 1/2" Female NPT or M20x1.5 entries.

Epoxy coated.

Operating Temperature: 0 °F to 140 °F [-18 °C to 60 °C]

Input Power:

DC: 18 Vdc to 36 Vdc (6 watts max.)

AC: 85 Vac to 265 Vac (12 watts max.; CE Mark Approval

for 100 Vac to 240 Vac)

Analog Output Signals: Dual 4-20 mA, configurable to

flow rate and/or temperature (500 ohm max impedance)

and a pulse output for total flow.

Output Pulse Source: Totalized flow or alarm set point.

15VDC. Pulse width at 50% duty cycle for rates 1 to

500Hz, 0.5 second pulse width for pulse rates below 1Hz.

25mA maximum load pulsed, 10mA maximum load if state

set to normally on.

Output Pulse Sink: Totalized flow or alarm set point. Pulse

width at 50% duty cycle for rates 1 to 500Hz, 0.5 second

pulse width for rates below 1Hz. Customer power source

and load not to exceed 40VDC and 150mA.

Communication Port: RS-232C. Wireless IR to PDA with

optional digital display models.

Digital Display: Two-line x 16 character LCD; displays

measured value and engineering units. Top line assigned to

flow rate, second line user assignable to temperature

reading, flow totalizer or alternating. Display can be

rotated in 90° increments for optimum viewing orientation.

Installation and Mounting: Integral with sensor element

or remote mountable

up to 50' [15 m].

Specifications