Bilinear output mode, Configure relays, Bilinear output mode configure relays – Hach-Lange POLYMETRON 9500 User Manual User Manual

Page 31

Advertising
background image

Bilinear output mode

Figure 15

shows in graph form the operation of the bilinear output mode.

Figure 15 Bilinear output

1 Output current axis

4 Knee point value

7 Knee point current

2 Source value axis

5 Low value

8 Maximum output current

(20 mA)

3 High value

6 Minimum output current

(0-4 mA)

Configure relays

The Normally Open (NO) and Common (COM) relay contacts will be connected when an alarm or
other condition is active. The Normally Closed (NC) and Common relay contacts will be connected
when an alarm or other condition is inactive (unless the FAIL SAFE is set to YES), or when power is
removed from the controller. To select a menu option, highlight the option and push enter.

1. Push the menu key and select Polymetron 9500 SETUP>RELAY SETUP.
2. Select a relay from the list.
3. From the RELAY SETUP menu, choose SELECT SOURCE and push enter. Normally, a source

is one of the sensors attached to the system, but the controller can also function as a source. If
an analog input module is installed, the source may be the analog input.

4. From the RELAY SETUP menu, select SET PARAMETER and choose from the list of

parameters. The list of parameter options will vary with the type of attached sensor.

5. From the RELAY SETUP menu, select SET FUNCTION and choose from the list. Further setup

will depend on the function chosen.

Option

Description

SCHEDULER (available if the
controller is selected as the
relay source)

Relay switches at certain times independently of any process value

ALARM

Relay activates when upper or lower alarm value is exceeded

FEEDER CONTROL

Relay indicates if a process value exceeds or falls below a setpoint

EVENT CONTROL

Relay toggles if a process value reaches an upper or lower limit

English 29

Advertising