Installation – Hach-Lange RTC112 SD-Module User Manual

Page 18

Advertising
background image

18

Installation

3.4

Connection to the automation unit on the plant side

The one-channel and two-channel versions of the RTC112 SD-Module are equipped with
various modules that must be connected to the plant automation system.

The feed flow rate must be provided to the RTC112 SD-Module as a 0/4 to 20 mA
signal.

The polymer flow rate must be provided (on both versions) to the RTC112 SD-Module
as a 0/4 to 20 mA signal.

The polymer pump can be operated in pulse/pause mode (PWM).

The status signals and fault indications are output as 0 V/24 V signals.

Measurement errors are shown 5 minutes after the error occurs. In the event of a new
startup (return of power supply), the unit is set back to ON (24 V) after approximately
1 minute and 40 seconds if there are no measurement errors.

In the event of a new startup (return of power supply), the RTC operating signal is set
back to ON (24 V) after approximately 1 minute and 25 seconds.

Table 3 Connections for the 1-channel RTC112 SD-Module

Module

Name

Connection Signal

Function

4x digital output

1

KL2134

1

+24 V/0 V

Polymer pump on/off (24 V/0 V); (LED a)

5

+24 V/0 V

Closed-loop control of the feed flow rate
active/inactive (24 V/0 V); (LED c)

4

+24 V/0 V

Input signals OK (24 V), input signal faulty (0 V);
(LED b)

8

+24 V/0 V

RTC operational (24 V), RTC faulty (0 V), (LED d)

2x analog output

KL4012

1(+) - 3(-)

0/4 to 20 mA

Output of the polymer pump flow rate

5(+) - 7(-)

0/4 to 20 mA

Output of the feed flow rate

1x analog input

KL3011

1(+) - 2(-)

0/4 to 20 mA

Input of the feed flow rate

1x analog input

KL3011

1(+) - 2(-)

0/4 to 20 mA

Input of the polymer flow rate

Bus termination

KL9010

Bus termination

1

Ground to connection 3 and 7 or to the supply voltage connections

Table 4 Connections for the 2-channel RTC112 SD-Module

Module

Name

Connection Signal

Channel

Function

8x digital
output

1

KL2408

1

+24 V/0 V

1

Polymer pump on/off (24 V/0 V) (LED a)

5

+24 V/0 V

1

Closed-loop control of the feed flow rate
active/inactive (24 V/0 V) (LED e)

2

+24 V/0 V

1

Input signals OK (24 V), input signal faulty (0 V)
(LED b)

6

+24 V/0 V

1

RTC operational (24 V), RTC faulty (0 V) (LED f)

3

+24 V/0 V

2

Polymer pump on/off (24 V/0 V) (LED c)

7

+24 V/0 V

2

Closed-loop control of the feed flow rate
active/inactive (24 V/0 V) (LED g)

4

+24 V/0 V

2

Input signals OK (24 V), input signal faulty (0 V)
(LED d)

8

+24 V/0 V

2

RTC operational (24 V), RTC faulty (0 V) (LED h)

2x analog
output

KL4012

1(+) - 3(-)

0/4 to 20 mA

1

Output of the polymer pump flow rate

5(+) - 7(-)

0/4 to 20 mA

1

Output of the feed flow rate