4.7

CONTROL PARAMETER

4.7.1

FACTOR POLYMER DOSING

Required specific polymer dosing [g/kg]. This parameter
determines how many grams of polymer per kilogram of TSS are
fed by the system.

4.7.2

POLYMER CONCENTRATION

Polymer concentration [g/L] fed via the polymer pump.

4.7.3

MANUAL POLYMER DOSING

The RTC outputs the polymer dosing rate [L/h] if

•

FEED FLOW CONTROL is activated

•

No open-loop control mode (

section 4.6.1

to

section 4.6.3

) is

activated

•

The TSS measurement from the influent reports an error, or

•

The flow measurement from the influent reports an error.

4.7.4

MANUAL FEED FLOW

The RTC outputs the feed flow rate [m

3

/h] if

•

POLYMER DOSING CONTROL is activated

•

No open-loop control mode (

section 4.6.1

to

section 4.6.3

) is

activated

•

The TSS measurement at the inlet reports an error, or

•

The flow measurement from the influent reports an error.

4.7.5

MAX DECREASE CLOSED L

This value defines the maximum decrease of the specific polymer
dosing rate FACTOR POLYMER DOSING [g/kg] if
CLOSED-LOOP EFFLUENT CONTROL is selected.

4.7.6

MAX INCREASE CLOSED L

This value defines the maximum increase of the specific polymer
dosing rate FACTOR POLYMER DOSING [g/kg] if
CLOSED-LOOP EFFLUENT CONTROL is selected.

4.7.7

SET-POINT TSS

Required setpoint of the TSS concentration in the dewatered
sludge.

Note: · This parameter is only considered if CLOSED-LOOP EFFLUENT
CONTROL (

section 4.6.3

) is activated.