7 control parameter, 1 factor polymer dosing, 2 polymer concentration – Hach-Lange RTC112 SD-Module User Manual

Page 30: 3 manual polymer dosing, 4 manual feed flow, 5 max decrease closed l, 6 max increase closed l, 7 set-point tss

Advertising
background image

30

Parameterization and operation

4.7

CONTROL PARAMETER

4.7.1

FACTOR POLYMER DOSING

Required specific polymer dosing [g/kg]. This parameter
determines how many grams of polymer per kilogram of TSS are
fed by the system.

4.7.2

POLYMER CONCENTRATION

Polymer concentration [g/L] fed via the polymer pump.

4.7.3

MANUAL POLYMER DOSING

The RTC outputs the polymer dosing rate [L/h] if

FEED FLOW CONTROL is activated

No open-loop control mode (

section 4.6.1

to

section 4.6.3

) is

activated

The TSS measurement from the influent reports an error, or

The flow measurement from the influent reports an error.

4.7.4

MANUAL FEED FLOW

The RTC outputs the feed flow rate [m

3

/h] if

POLYMER DOSING CONTROL is activated

No open-loop control mode (

section 4.6.1

to

section 4.6.3

) is

activated

The TSS measurement at the inlet reports an error, or

The flow measurement from the influent reports an error.

4.7.5

MAX DECREASE CLOSED L

This value defines the maximum decrease of the specific polymer
dosing rate FACTOR POLYMER DOSING [g/kg] if
CLOSED-LOOP EFFLUENT CONTROL is selected.

4.7.6

MAX INCREASE CLOSED L

This value defines the maximum increase of the specific polymer
dosing rate FACTOR POLYMER DOSING [g/kg] if
CLOSED-LOOP EFFLUENT CONTROL is selected.

4.7.7

SET-POINT TSS

Required setpoint of the TSS concentration in the dewatered
sludge.

Note: · This parameter is only considered if CLOSED-LOOP EFFLUENT
CONTROL (

section 4.6.3

) is activated.