24

Parameterization and operation

DERIVATIVE TIME FILT

Derivative time for the PID closed-loop controller for the TSS
concentration in the centrate/filtrate.

Note: This parameter is only considered if CLOSED-LOOP
FILTRATE CONTROL is activated.

min

CHANNEL 2

As per channel one

INPUT/OUTPUT LIMITS

CHANNEL 1

FEED FLOW LOW

Feed flow rate input signals below this value [m

3

/h] are set to

this value (to avoid low flow peaks).

m

3

/h

FEED FLOW HIGH

Feed flow rate input signals above this value [m

3

/h] are set to

this value (to avoid high flow peaks).

m

3

/h

FEED FLOW SMOOTHING

Feed flow measurement values are smoothed in line with this
parameter.

min

LIMIT TSS IN LOW

TSS measurement values from the influent that are below this
value [g/L] are set to this value (to avoid low peaks).

g/L

LIMIT MAX TSS IN HIGH

TSS measurement values from the influent that are above this
value [g/L] are set to this value (to avoid high peaks).

g/L

TSS IN SMOOTHING

The TSS measurement values from the influent are smoothed in
line with this parameter.

min

LIMIT TSS OUT LOW

The TSS values of the dewatered sludge or centrate sludge that
are below this value [g/L] are set to this value (to avoid low
peaks).

g/L

LIMIT TSS OUT HIGH

The TSS values of the dewatered sludge or centrate sludge that
are above this value [g/L] are set to this value (to avoid high
peaks).

g/L

TSS OUT SMOOTHING

The TSS measurement values from the effluent are smoothed in
line with this parameter.

min

POLYMER DOSING
MINIMUM

When FEED FLOW CONTROL is activated, measurement
values for the polymer dosing rate that are below this value
[m³/h] are set to this value (to avoid low peaks in the dosing
flow).

L/h

POLYMER DOSING
MAXIMUM

Any RTC calculation above this value [g/L] is set to this value
and delivered to the polymer pump.
When FEED FLOW CONTROL is activated, measurement
values for the polymer dosing rate that are above this value
[m³/h] are set to this value (to avoid high peaks in the dosing
flow).

L/h

CHANNEL 2

As per channel one

4.4.1

RTC112 SD-Module open and closed-loop controller (Continued)

RTC MODULES / PROGNOSYS

RTC MODULES