2 feed flow high, 3 feed flow smoothing, 4 limit tss in low – Hach-Lange RTC112 SD-Module User Manual

Page 32: 5 limit max tss in high, 6 tss in smoothing, 7 limit tss out low, 8 limit tss out high

Advertising
background image

32

Parameterization and operation

4.8.2

FEED FLOW HIGH

Feed flow rate input signals above this value [m

3

/h] are set to this

value. This avoids load peaks.

4.8.3

FEED FLOW SMOOTHING

Feed flow measurement values are smoothed in line with this
parameter.

SMOOTHING = 1: The signal for the flow rate measurement
is not smoothed.

SMOOTHING = 2: Smoothing is performed over 3 minutes.

SMOOTHING = 3: Smoothing is performed over 5 minutes.

SMOOTHING = 5: Smoothing is performed over 12 minutes.

SMOOTHING = 10: Smoothing is performed over
25 minutes.

Example:

With the setting SMOOTHING = 2, it takes 3 minutes for the
smoothed value to reach 95 % of the final value after an abrupt
change in the feed flow rate.

4.8.4

LIMIT TSS IN LOW

TSS measurement values from the influent that are below this
value [g/L] are set to this value (to avoid low peaks).

4.8.5

LIMIT MAX TSS IN HIGH

Measurement values from the influent that are above this value
[g/L] are set to this value (to avoid high peaks).

4.8.6

TSS IN SMOOTHING

TSS measurement values from the influent are smoothed in line
with this parameter.

SMOOTHING = 1: The signal is not smoothed.

SMOOTHING = 2: Smoothing is performed over 3 minutes.

SMOOTHING = 3: Smoothing is performed over 5 minutes.

SMOOTHING = 5: Smoothing is performed over 12 minutes.

SMOOTHING = 10: Smoothing is performed over
25 minutes.

4.8.7

LIMIT TSS OUT LOW

TSS measurement values for the dewatered sludge or centrate
that are below this value [g/L] are set to this value (to avoid low
peaks).

4.8.8

LIMIT TSS OUT HIGH

TSS measurement values for the dewatered sludge or centrate
that are above this value [m

3

/h] are set to this value (to avoid high

peaks).

Advertising