9 tss out smoothing, 10 polymer dosing minimum, 11 polymer dosing maximum – Hach-Lange RTC112 SD-Module User Manual

Page 33: 9 inputs, 1 min feed flow, 2 max feed flow, 3 0/4 ma, 4 min polymer flow, 5 max polymer flow

Advertising
background image

33

Parameterization and operation

4.8.9

TSS OUT SMOOTHING

TSS measurement values from the effluent are smoothed in line
with this parameter.

SMOOTHING = 1: The signal is not smoothed.

SMOOTHING = 2: Smoothing is performed over 3 minutes.

SMOOTHING = 3: Smoothing is performed over 5 minutes.

SMOOTHING = 5: Smoothing is performed over 12 minutes.

SMOOTHING = 10: Smoothing is performed over
25 minutes.

4.8.10 POLYMER DOSING MINIMUM

RTC calculations below this value [g/L] are set to this value and
transferred to the polymer pump.

Note: When FEED FLOW CONTROL is activated, measurement values
for the polymer dosing rate that are below this value [m

3

/h] are set to this

value (to avoid low peaks in the dosing flow).

4.8.11 POLYMER DOSING MAXIMUM

RTC calculations above this value [g/L] are set to this value and
transferred to the polymer pump.

Note: When FEED FLOW CONTROL is activated, measurement values
for the polymer dosing rate that are above this value [m

3

/h] are set to this

value (to avoid high peaks in the dosing flow).

4.9

INPUTS

4.9.1

MIN FEED FLOW

Minimum flow rate [m³/h] from the influent in accordance with the
0/4 mA measurement signal.

4.9.2

MAX FEED FLOW

Maximum flow rate [m³/h] from the influent in accordance with the
20 mA measurement signal.

4.9.3

0/4...20 mA

Transfer range of the 0/4 to 20 mA current loop (as set in
connected flow measuring instrument).

4.9.4

MIN POLYMER FLOW

Minimum polymer dosing in [L/h] in accordance with the 0/4 mA
measurement signal.

4.9.5

MAX POLYMER FLOW

Maximum polymer dosing in [L/h] in accordance with the 20 mA
measurement signal.