PRESELECT PROG.

CHANNEL 1

POLYMER DOSING
CONTROL

Based on the feed flow rate [m³/h] and measured TSS
concentration [g/L] from the influent, the polymer dosing rate
[L/h] is calculated such that it corresponds to the target specific
polymer dosing rate [g/kg].

Activation/

deactivation

FEED FLOW CONTROL

Based on the measured TSS concentration [g/L] and a fixed
polymer dosing rate [L/h], the feed flow [m

3

/h] is calculated such

that it corresponds to the specific polymer dosing rate [g/kg].

Activation/

deactivation

CLOSED-LOOP EFFLUENT
CONTROL

If activated, the specific polymer dosing rate FACTOR
POLYMER DOSING is adjusted based on the difference
between the target and actual TSS concentration in the
dewatered sludge.
The change in the specific dosing rate affects the polymer
dosing rate [L/h] in the POLYMER DOSING CONTROL module
or affects the feed flow rate in the FEED FLOW CONTROL
module.

Activation/

deactivation

CLOSED-LOOP FILTRATE
CONTROL

If activated, the specific polymer dosing rate FACTOR
POLYMER DOSING is adjusted based on the difference
between the target and actual TSS concentration in the
filtrate/centrate.
The change in the specific dosing rate affects the polymer
dosing rate [L/h] in the POLYMER DOSING CONTROL module
or affects the feed flow rate in the FEED FLOW CONTROL
module.

Note: Activation and deactivation of CLOSED-LOOP
EFFLUENT CONTROL and CLOSED-LOOP FILTRATE
CONTROL have to be prepared by executing the relevant
*bat-files on the RTC CF-card (see

section 2.5.3

).

Activation/

deactivation

CHANNEL 2

As per channel one

CONTROL PARAMETER

CHANNEL 1

FACTOR POLYMER
DOSING

Required specific polymer dosing [g/kg]. This parameter
determines how many grams of polymer per kilogram of TSS
are fed by the machine.

g/kg

POLYMER CONCEN-

TRATION

Polymer concentration [g/L] fed via the polymer pump.

g/L

MANUAL POLYMER
DOSING

The RTC outputs the polymer flow rate [L/h] if

FEED FLOW CONTROL is activated

No open-loop control mode (see above) is activated

The TSS measurement from the influent reports an error, or

The flow measurement from the influent reports an error.

L/h

MANUAL FEED FLOW

The RTC outputs the feed flow rate [m³/h] if

POLYMER DOSING CONTROL is activated

No open-loop control mode (see above) is activated

The TSS measurement from the influent reports an error, or

The flow measurement from the influent reports an error

m³/h