Parameterization and operation

INPUTS

CHANNEL 1

MIN FEED FLOW

Minimum flow rate [m³/h] from the influent in accordance with
the 0/4 mA measurement signal.

m³/h

MAX FEED FLOW

Maximum flow rate [m³/h] from the influent in accordance with
the 20 mA measurement signal.

m³/h

0/4...20mA

Transfer range of 0/4 to 20 mA current loop (as set in connected
flow measuring instrument).

MIN POLYMER FLOW

Minimum polymer dosing in [L/h] in accordance with the 0/4 mA
measurement signal.

L/h

MAX POLYMER FLOW

Maximum polymer dosing in [L/h] in accordance with the 20 mA
measurement signal.

L/h

0/4...20mA

Transfer range of 0/4 to 20 mA current loop (as set on
connected flow measuring instrument).

CHANNEL 2

As per channel one

OUTPUTS

CHANNEL 1

MIN FEED FLOW

Minimum feed flow rate [m³/h] in accordance with 0/4 mA.

m³/h

MAX FEED FLOW

Maximum feed flow rate [m³/h] in accordance with 20 mA.

m³/h

0/4...20mA

Transfer range of 0/4 to 20 mA current loop (as set on
connected flow measuring instrument).

MIN POLYMER FLOW

Minimum polymer pump delivery rate in accordance with
0/4 mA.

L/h

MAX POLYMER FLOW

Maximum polymer pump delivery rate in accordance with
20 mA.

L/h

0/4...20mA

Transfer range of 0/4 to 20 mA current loop (as set on
connected flow measuring instrument).

CONTROL CYCLE

Pulse/pause mode for the polymer pump open-loop control for
dosing rates beneath the minimum polymer flow rate (MIN
POLYMER FLOW). The on/off duration in pulse/pause mode
can be affected by the duration of the CONTROL CYCLE. For
example, with a CONTROL CYCLE of 100 seconds and a
dosing control value of 60 %, the polymer pump is regularly
switched on for 60 seconds and switched off for 40 seconds.
Short cycle times increase the switching frequency but enable
more precise adaptation to individual requirements. CONTROL
CYCLE should be divisible by MIN RUNTIME and produce a
whole number.

s

MIN RUNTIME

The minimum ON time in pulse/pause dosing mode. The pump
is not activated for periods shorter than this. The MIN RUNTIME
must be shorter than the duration of the CONTROL CYCLE.

s

CHANNEL 2

As per channel one

4.4.1

RTC112 SD-Module open and closed-loop controller (Continued)

RTC MODULES / PROGNOSYS

RTC MODULES