Lobby Hall Up Call Relay

The Lobby Hall Up Call Relay (terminals 69-70) is a special relay that activates when access has
been granted and "calls" the elevator car to the lobby or ground floor.

• Be sure that the lobby hall call relay is set for Normally Open (N.O.) operation.
• SW-2, switch 8 must be in the OFF position for the LOBBY HALL CALL function to operate.

NOTE: If the LOBBY HALL CALL relay function is used (SW-2, switch 8 OFF), then the
elevator detect switch must be connected to the 2348-010 control board (see 3.2.4).

4.4.4

Ground Floor Detect Switch

The ground floor detect switch signals the 2348-010 elevator control board that the elevator car has
arrived at the lobby or ground floor. This signal is in the form of a switch closure across terminals 17
and 18 and may be available from existing hardware in the elevator electronics panel. Consult with
the elevator service technician regarding this switch input.

• Connect a Normally Open (N.O.) ground floor detect switch to terminals 17 and 18 (fig 7).
• Note: Dry contact - no voltage.
• The switch must activate when the elevator car is at the lobby or ground floor.

4.4.5

Resident Elevator Access Device

Each elevator car that is controlled by the access system must have an access device (card reader,
keypad, etc.) installed in the elevator car so that the access system knows which floor(s) the resident
is to be granted access to.

• Installing the access device in the elevator car should be coordinated with the elevator

service company since wiring from the access device inside the elevator car will have to be
routed along the elevator electrical umbilical cable to the access controller.

• Refer to the access control system installation manual for additional wiring instructions.
• Route the wiring from the access device to the access control system via the elevator

electrical umbilical (fig. 8).

• Connect this wiring as specified in the access control system installation manual. There is no

direct connection of the access device to the 2348-010 Elevator Control Board.