SECTION 2

HPN-IOM-2014-0416

INSTALLATION

2-5

TABLE 3- MINIMUM MAKE-UP AIR REQUIREMENTS AND RECOMMENDED AREA OF OPENING

FOR VENTS

Model

Minimum Make-Up

Air (SCFM)*

Opening Area (in

2

)**

Lower Vent

Opening Area (in

2

)

Upper Vent

100

300

600

200

200

600

1200

400

350

1000

2000

667

600

1800

3600

1200

800

2300

4600

1534

1000

2900

5800

1934

1200

3500

7000

2334

1400

4000

8000

2667

1600

4600

9200

3067

2000

5800

11600

3867

2400

6900

13800

4600

3000

8600

17200

5734

4000

11500

23000

7667

* Minimum make-up air requirements are based on 25% excess air at high fi re.

** Opening areas are calculated based input of a single heater and do not

account for the ventilation needs of the equipment room. These measurements

are subject to state and local regulations.

C

A

B

FIGURE 2 - DIMENSIONS

Model

Heater Only

(lbs/ft2)

100

129

200

143

350

143

600

151

800

123

1000

155

1200

132

1400

129

1600

131

2000

145

2400

176

3000

194

4000

190

TABLE 2 - APPROXIMATE FLOOR LOADING

(BASED ON OPERATING WEIGHT)