Siemens Linkageless Modulation, LMV 51

SETTING PILOT

1. Verify the main burner switch is in the OFF position.

2. Supply power to the heater. The AZL will display “system test” and then

move to the main menu.

3. Select

PWLogin, press Enter. Select AccessServ. Press Enter. (This type

of step will be shown as PWLogin > AccessServ for the remainder of this
section. Enter the service passwords using the arrow key. The password is
case sensitive. The case of a letter can be changed by pressing the other
arrow key. (For example, if you used the right arrow key to get to the
letter A, press the left arrow key to get a). After you have pressed Enter on
the last character of the password, press Enter once more to accept the
password. If you do not have the password, contact your Fulton Authorized
Representative to perform the changes. Service=NB# or OEM=AAAA (Enter
after each A).

4. Select

Params&Display. Press Enter. Select Ratio Control. Press Enter.

Select ProgramStop. Press Enter. Change the Program Stop to 44
Interv1
by using the arrow keys. Confi rm the change by pressing Enter.
This will set the burner management system to a ‘pilot hold’ setting.

5. Verify that the current value “curr” changes to 44 Interv 1.

6. The full listing of program stops are:

» 24: Air damper in the prepurge position

» 32: Traveling to the FGR position

» 36: Ignition position (before pilot ignition)

» 44: Ignition position (after pilot ignition)

» 52: Ignition position (after main burner ignition)

» 72: Air damper in the postpurge position

» 76: Traveling to the FGR position

7. Press

Escape 4 times to get back to the main menu.

8. Under

ManualOperation > Setload, change the load to 0% by using the

arrow keys. Press Enter and verify the 0% has been acknowledged in the
curr” fi eld.

9. Press

Escape once to get back to the ManualOperation menu.

10. Under

Auto/Manual/Off , change the operation to Burner On by using the

arrow keys. Press enter and verify that “Burner On” is acknowledged in the
current fi eld.

11. Press

Escape twice to get back to the main menu.

12. Turn the main burner switch Local or On position.