SECTION 3

HPN-IOM-2014-0416

OPERATION

3-13

4

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.

Gas to Oil

1. Turn

off the manual gas cocks in the gas train.

2. Remove the gas nozzle orifi ce assembly from the burner.

3. Install the oil nozzle assembly and attach the oil whips to the assembly.

4. Open all oil manual shutoff valves.

5. Set the fuel selector switch to the proper fuel. Restart unit normally

Oil to Gas

1. Turn

off all oil manual shutoff valves.

2. Detach the oil whips and remove the oil nozzle assembly.

3. Install the gas nozzle orifi ce assembly and open the gas cocks in the gas

train.

4. Reset the hi/low gas pressure switch.

5. Set the fuel selector switch to the proper fuel. Restart unit normally.

Flame Programmers

Fireye Linkage Modulation, YB110/E110

The Fireye Linkage Controls come complete and wired from the factory, with
no programming necessary. Please refer to the Fireye cut sheet for specifi c
programmer information.

GASFIRED/DUAL FUEL UNITS

Gas-fi red/dual fuel units come with a UV Scanner and amplifi er module as
standard. Self-checking scanners are off ered as an option by request.

OILFIRED UNITS

Oil-fi red units come with an IR Scanner and amplifi er module as standard.

YZ300/E300 ANNUNCIATOR

Most Fulton units come with the YZ300/E300 expansion module with panel-
mounted display. This display will read fi rst out annunciation of any recycled or
safety limits wired into the Fireye module.

Both annunciators come pre-programmed from Fulton with application specifi c
display messages. Please refer to Fireye cut sheet or contact Fulton for assistance
with annunciator programming.