Installation, Instrument air, Electrical supply – Fulton Hopkins (HPN) Horizontal Coil Thermal Fluid (hot oil) Heater User Manual

Page 13: The oil supply

Advertising
background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

SECTION 2

HPN-IOM-2014-0416

INSTALLATION

2-7

or another unit.The burner assembly and gas controls
terminate at a manual stop valve to which the gas
supply should be connected. Piping must be sized
for a gas fl ow consistent with the required BTU/Hr
input. Large pressure drops must be avoided. Fulton
recommends that the supply piping between the
pressure regulator and the inlet to the heater be kept to
a minimum. The minimum required gas pressure at the
stop valve varies with the model of heater.

NOTE:

Even when the unit is shut down, the gas supply

pressure must never exceed these values.

11. Some fuel train confi gurations are require a safety relief

valve which must be piped to a safe area in accordance
with local codes.

12. After gas piping is completed and before wiring

installation is started, carefully check all piping
connections, (factory and fi eld), for gas leaks. Use a soap
and water solution.

The Oil Supply

Fuel Oil

Viscosity

Specifi c Gravity

Sulfur Content

#2

Less than

31.9 Seconds

Redwood #1 at

100°F (38°C)

0.824 to 0.852 at

59 C (15°C)

less than 0.40%

by weight

#4

Less than

81 Seconds

Redwood #1 at

100°F (38°C)

0.90 to 0.93 at 59

C (15°C)

less than 0.1.6%

by weight

#6

Less than 3000
Seconds Red-
wood #1 at 100°F
(38°C)

0.95 to 0.98 at
59°F (15°C)

less than 2.12%
by weight

Adhere to the following for installation:

1. Fuel pipes must be of approved materials and of a

diameter suitable for the quantity of oil being delivered to
the burner and the static head available.

2. Make fuel connection in accordance with the details on

the enclosed fuel pump cut sheet.

3. Ensure fuel oil piping is in accordance with local and/or

national requirements. In addition, if a two pipe system
is employed, a check valve must be fi tted into the return
pipe.

4. Do not exceed the 3 psi maximum pressure allowed at

the fuel oil pump inlet per the National Fire Protection
Association (NFPA).

NOTE:

If for some reason the pressure of the fuel supply will

exceed NFPA maximum, fi tting a regulator to the fuel line
must be considered, e.g. when there is a tank situated with an
oil level eight feet (2.4 m) or more above the pump.

5. On units fi tted with NFPA controls, ignition is obtained by

means of a gas pilot. A natural gas or LP supply is required
for these units. The required gas supply pressure is 7” w.c.
If a guaranteed supply of natural gas is not available, then
a supply of bottled gas at 11“w.c. is required. For details
contact a local liquid propane dealer.

Instrument Air

Instrument air provision for pneumatically actuated control
devices should meet the minimum and maximum fl ow rate
and delivery pressures specifi ed by the individual equipment.
Additionally, it should be a dry, dust-free,water-free, and oil-
free supply with a dew point of -40°F (-40°C).

Electrical Supply

Adhere to the following for electrical supply installation:

1. Install wiring and ground in equipment in accordance

with authority having jurisdiction or in absence of such
requirements the National Electrical Code, ANSI/NFPA 70.

2. Provide a wall-mounted, fused disconnect sized for

the unit. This must be fi tted by the client/contractor if
disconnect is not supplied on the panel.

3. Size fuses according to motor name plates and local

electrical codes.

4. Connect power to the terminal strip as supplied on the

inside of the panel box.

NOTE:

Single skid systems are generally shipped completely

prewired.

NOTE:

The liquid level switch on the expansion tank, when

supplied, will be shipped in the parts box and must be
installed in the fi eld.

5. Determine multiple skid systems wiring requirements

(between the skids). Fulton will run conduit and wire
the devices on each skid. For the devices that have to

Advertising