Installation – Fulton Hopkins (HPN) Horizontal Coil Thermal Fluid (hot oil) Heater User Manual

Page 28

Advertising
background image

© The Fulton Companies 2014

INSTALLATION

HPN-IOM-2014-0416

SECTION 2

2-22

!

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.

Pressure Gauges

The range in which readings are expected to fall should comprise mid-scale on
the pressure gauge chosen (See Figure 12). Pressure gauges must be able to
withstand overpressure equal to the rating of the safety relief valves, normally
100 psig.

Thermometers

Thermometers should read up to 650°F (343°C). For systems with higher
operating temperatures, select thermometers accordingly.

FIGURE 11 - DRAIN AND FILL CONNECTION

FIGURE 10 - LIQUID LEVEL SWITCH LOCATION

Advertising