INSTALLATION

HPN-IOM-2014-0416

SECTION 2

2-20

2. Under normal operating conditions, the catch tank

should be empty. Fluid that is expelled into the tank
should not be reintroduced into the system.

3. Ensure the vent from the catch tank is located and

installed in such a manner as to protect personnel and
property from discharge of steam, water, and thermal
fl uid. Vent outlet should be positioned in a safe location
outside the heater room.

Drain/Fill Connection

The system is usually fi lled from the lowest point, with the aid
of a pump. On skid-mounted units, a drain and fi ll connection
is provided in the inlet piping to the pump. See Figure 11.

11. An inspection opening is located at the highest point

on the tank. Access to this port is recommended but
not required.

12. Refer to the maintenance schedule for

recommendations on draining the buff er tank. For
positioning of all connections on tank, see Figure 9.

Catch Tank

Adhere to the following for the catch tank:

1. Ensure the heater safety relief valve outlet and

connections on the DA tank are piped to a safe catch
tank. The catch tank must be appropriately sized based
on the system volume and confi guration.

Vent for Piping

to Safe Catchment

Expansion

Tank

Liquid

Level

Switch

Fluid Out

Fluid In

Deaerator

Section

Thermal
Buffer
Section

Hot Fluid

Medium Fluid

Cool Fluid

Gases (Steam)

Expansion

Volume

Drain

Model

Capacity (gallons)

Initial Fill (gallons)

Available for

Expansion (gallons)

Max System

Volume

FT-200-L

52

25

46

184

FT-500-L

132

40

121

525

FT-1000-L

264

80

232

1000

FT-1500-L

397

90

380

1400

FT-2000-L

528

145

444

1700

FT-3000-L

793

215

717

2600

FT-5000-L

1310

300

1168

4600

FIGURE 8 - EXPANSION TANK DETAILS