CLASS 1000 METER

13

62-0388-01

4.5 Installing the Solid-Core Current Sensor Assembly

The optional solid-core current sensors can be installed in the same applications as

the standard split-core units, however, the conductors that they are monitoring must

first be disconnected.

NOTE: Under no circumstances is this operation to take place without shutting off the

power to the conductor(s) being monitored.

With the power off, disconnect the conductor from its breaker or terminal. Slide the

solid-core current sensor over the conductor, making sure that the indicator on the

sensor is pointing in the direction of the load. After this is done, reconnect the

conductor and verify that it is properly installed.

Run the black and white wires from the solid-core current sensors and install them

according to the standard installation diagram. When this is completed, the power to

the monitored conductor can be turned back on.

Fig. 5. Solid Core Sensor Assembly