4.0 METER INSTALLATION

4.1 Mounting the Meter

STEP 1: Using the appropriate sized mounting hardware, fasten the Class 1000 meter

enclosure to the selected mounting surface. The four mounting holes are centered

6.75” H x 4” W. The mounting hole spacing is identical for either the UL Type 1 or

NEMA 4X enclosure.

NOTE: Only the NEMA 4X enclosed unit is suitable for outdoor environmental condi-

tions. Units housed in UL Type 1 enclosures must only be installed in indoor

environments where it will not be affected by the elements, such as moisture

and extreme temperatures.

4.2 Main Power Board Connections

STEP 1: Install a temporary ground for ESD (Electrostatic Discharge) protection. With

all circuits de-energized, connect a temporary protective earth ground connection for

ESD protection. Prior to performing any unit wiring, be sure to discharge any static on

your person.

STEP 2: Install the Class 1000 Protective Earth Ground. Connect an earth ground wire

to the Class 1000 protective earth ground terminal screw located on the right side of

the line voltage terminal block. After installing the protective earth ground wire,

securely fasten the protective earth ground screw.