E-Mon E10-2277200JKIT User Manual

Page 29

Advertising
background image

CLASS 1000 METER

29

62-0388-01

Altitude

2000 Meters Maximum

Voltage Overload

+25% Continuously: +100% For 20 Cycles

Current Sensor

Overload

100% For 1 Minute Without Damaging Meter

Pollution Degree

Degree 2 In Accordance With IEC 664

Installation

(Overvoltage)

Category

Category 3

Measurement

Category

Category 3

Enclosure Material

Indoor Housing Rating (Standard): UL Type 1

Outdoor Housing Rating (Optional): NEMA 4X

Display Readout

KWh Accumulated, Instantaneous kW

Standard Ranges

3-wire 115/208 Vac; 25,50,100, 200

2 Phase 120/240 Vac; 25,50,100, 200, 400

IDR Interface Port

Cable Specification: UL-listed/rated

Telephone

Cord. 6 conductor.

Input/output Voltage:

+5 VDC/18 VAC

Cable Connector:

RJ-45 male IDC

Circuit Input Isolation:

5.3kVAC for one minute

Circuit output Isolation:

2.5kVAC

Isolated Pulse/Alarm

Outputs

Output Voltage Potential:

0 VDC to +5 VDC Logic Levels

Mating Plug Connector:

Weidmuller PN: 152876

Signal Isolation Voltage:

5.3K VAC for 1 Minute

Recommended

In-line Fuse

Manufacturer: Littlefuse

Mfg. Part No.:

KLDR.100

Rating:

100mA, Time-delay, 600VAC

Cartridge Fuse

Advertising