9 final main board checks – E-Mon E10-2277200JKIT User Manual

Page 17

Advertising
background image

CLASS 1000 METER

17

62-0388-01

Verify that the current sensor white and black conductors are installed in the correct

header positions.

Verify that the current sensors are installed in the correct direction on the conductor

being monitored.

Verify that the current sensor plugs are terminated in the correct header on the Main

power board.

If the error LED still hasn’t been cleared, measure the AC voltage inputs across the

plug terminals of each current sensor, individually. Set the AC voltmeter to the 20 Volt

scale. If a reading of zero volts is indicated on the voltmeter, check for an open circuit.

An open connection could exist at the plug terminals or at a splicing junction. Also

verify a tight connection exists between the core halves.

If error message is still appearing, contact E-Mon technical support at (800) 334-3666

for further assistance.

4.9 Final Main Board Checks

Once the wiring error has been corrected, the Main Power Board error LED should

extinguish.