4.8 Line Voltage/Current Sensor Diagnostics

Fig. 8. Main Board Configuration

If the meter is not correctly wired, the “ERROR” indicator will be on.

Verify that the AC MAINS voltage wires are all connected to the correct positions on

the terminal block. Inspect the MAINS input wiring to verify each conductor is

terminated at the correct terminal block position. Using an AC voltmeter, measure the

AC voltage for each Phase to Neutral terminal and to the Frame ground point.

Verify each current sensor by running at least 1% of the full scale rated current through

the conductor being monitored by each phase. (e.g. 2 amp load required for each

phase to perform sensor diagnostic procedures.)