FEC AFC1200 User Manual

Page 15

Advertising
background image

)(& ,QF

9.4

AXIS UNIT ABNORMAL

ZERO CHECK ABNORMAL

CAL CHECK ABNORMAL

OFFSET CHECK ABNORMAL PRESET DATA ABNORMAL
ENCODER ANGLE PULSE ABNORMAL

MOTOR Over TEMPERATURE

ABNORMAL
TOOL Is NOT CONNECTED

SERVO ALARM

FULL SCALE TORQUE OVER ABNORMAL PREAMP EEPROM READ ABNORMAL
TOOL TYPE MISMATCH ABNORMAL

DUAL PORT RAM ABNORMAL

Input Power Over Abnormal

Servo I/F Power Supply Abnormal

Servo Type Abnormal

* Axis Unit Lockout (No Display)

NOTE: Whenever an Abnormal condition occurs related to the Axis Unit, the Axis Unit

Abnormal displays must be checked for any related Axis Unit display codes. Refer to
Section 9.6.1 prior to performing any corrective maintenance.

9.4.1 ZERO CHECK ABNORMAL ( axis Unit display code "a1" )

<ERROR DESCRIPTION>

the Zero level of the tool transducer is outside the acceptable limits. The following table
details the limits of the check for various equipment conditions.

If the Zero level check is not sequence-initiated, the
System will still perform a Zero level self-check at the
beginning of each fastening cycle. In this case the
Zero level must be within ± 0.250 VDC of the value
detected during power on of the equipment.

Zero level check while the Zero Check
function is not enabled via the sequence
program. Performed at the beginning
of each fastening cycle.

The Zero level during a sequence-initiated Zero check
must be within ± 0.125 VDC of the value detected
during power on of the equipment.

Zero level check while the Zero Check
function is enabled via the sequence
program. Performed at the beginning of
each fastening cycle.

The Zero level during a PLC-initiated self-check must
be within ± 0.125 VDC of the value detected during
power on of the equipment.

Zero level check while the PLC Self-
Check input is enabled, or the Main Unit
Manual RESET is activated.

Zero level must be between -2 VDC and +2 VDC.
The detected value is loaded into memory for
comparison during other Zero level checks.

Zero level check at power on.

<CHECK ITEMS>

1. Verify that the tool is properly secured to the mounting plate, and that there is no sign of

stress or misalignment. Ensure that there is no tool movement while the self-check is
being performed.

2. Verify that the homerun (sensor) cable is in good condition and is properly connected to

the Axis Unit and the tool (preamp).

3. ensure that the ISA Main and Axis Units are not located near any strong electrical or

magnetic fields.

4. Verify correct Axis Unit input power (200~230 VAC +/- 10%, 50/60 Hz, 3-phase) and

ensure that the power cable is in good condition and is properly connected.

5. If the problem still exists, replace the tool (homerun) cables with a set that is known to be

good. A spare cable set is normally provided with each System. (Refer to Section 8.3.5)

6. If the problem still exists, replace the affected tool. (Refer to Section 8.3.4)

7. If the problem persists, replace the affected AXIS UNit. (Refer to Section 8.3.3)

Chapter 9: Troubleshooting

Page 9-15

Advertising