Rev 1.0 Series X11CA Hardware Manual

2. X11CA Hardware Setup

Hardware Control-© 2002 Ronan Engineering

25

Upon the power application, the flasher module within the system will automatically
initiate reset cycle. If all the associated field contacts are in normal condition, the
system should then be in a quiescent state with the horn(s) off and no lamps flashing.

Press the TEST button.

(Refer to the sequence charts on the CD for the expected results.)


2.8 Troubleshooting

2.8.1 General

§ No light – Check for the burned out, broken or improperly seated bulbs.
§ Not functioning alarm points – Make sure that the alarm modules are

properly seated in their connector.

§ Power supply fuse blows each time power is applied.

a. Check the Power Supply Parts List or the unit instrument tag for

proper fuse size.

b. Remove the alarm system from the supply and try again. If fuse

holds, double check polarity and reconnect. If the fuse still blows,
remove all alarm modules and flasher and try again. If the fuse blows
at this point, the problem has been isolated to a short in the internal
wiring.

2.8.2. Non-operating Alarm System

§ Verify that the power source is functioning properly/
§ The plus to minus voltage on the rear terminals is in the range of 18V to

28V.

§ Verity each polarity.