Rev 1.0 Series X11CA Hardware Manual

3. Event Sequences

Hardware Control-© 2002 Ronan Engineering

34

3.4.4 F2A -1

First out automatic reset.

The first alarm operates as a basic Sequence A. subsequent alarms operate as a
status lamp and also activates the audible devices. Option 1 must be used to
enable the apparent operation of the audible for subsequent alarms. Subsequent
alarms are locked-in and cannot return to the normal state until the Acknowledge
pushbutton is activated, resetting the first out-alarm. After the inputs return to
normal and acknowledgement, all input points return to the normal sequence state
automatically.

Key applications:

1. First-out Alarm is of prime importance.
2. Subsequent alarms must lock-in and resound the audible if it has been

silenced.

3. If Option 1 is used, the number of concurrent alarms expected is small

enough that flashing is not required to locate each new subsequent
alarm when the audible sounds.