Rev 1.0 Series X11CA Hardware Manual

1. Overview

Hardware Control-© 2002 Ronan Engineering

3

1.2 Revision History

Revision 0.1

:

First Draft

Revision 0.2

:

Second Draft

Revision 1.0

:

First approved and released document

1.3 References

QA400

:

Design Control

QA4000

:

Design Development Quality Assurance Plan

QA4500

:

Project Archive

X11CA-3000

:

X11CA-IM Master Modules

X11CA-3001-IOM

:

X11CA Configuration Software User’s Manual

1.4 Specifications and Power Requirements

1.4.1 System Voltage

§ Lamps, Logic – 24 Vdc

±

20%

§ Field contacts – 24 Vdc, 48 Vdc, 125 Vdc, 115 Vac, or 240 Vac

1.4.2 Power Source (System External)

§ Power Supply – 115 Vac 50/60 Hz; 240 Vac 50/60 Hz
§ Converter – 24 Vdc, 48 Vdc, or 125 Vdc

To specify the correct power supply, count the number of alarm modules
you need to power from the supply. Calculate the total requirements as
follows.

Total Watts = Number of Modules x Factor F + (F Aux.) + P (IM)

Model

F Lamps

F LEDs

F Aux.

Relay

Adder

P (IM)

X16PDM

10.5 W

7.0 W

4 W

10 W

Match the total wattage with the next higher power rating of the Power
Supply or Converter listed.