Rev 1.0 Series X11CA Hardware Manual

3. Event Sequences

Hardware Control-© 2002 Ronan Engineering

35

3.4.5 F2M-1

First Out Manual Reset

The First out alarm operates as a basic sequence M. Subsequent alarms operate as
a status lamp and also operate the audible. Before acknowledging the First out
alarm, sequence F2M operates the same as sequence F2A. After
acknowledgement, sequence F2M differs by requiring a Reset to return to normal
even though the events have returned to normal.