Rev 1.0 Series X11CA Hardware Manual

1. Overview

Hardware Control-© 2002 Ronan Engineering

4

1.4.3 Temperature Range

§ Operating – 0

°

to 60

°

C (32

°

to 140

°

F)

§ Storage - -40

°

to +85

°

C (-40

°

to + 185

°

F)

1.4.4 Inputs

§ Contact – Dry or Live; Normally Open / Normally Closed
§ Field Selectable
§ Interrogation Voltage – 24 Vdc, 48 Vdc, 125 Vdc, 115 Vac, or 240

Vac

1.4.5 Response Time

§ 20 Milliseconds by default. It can be modified using the X11CA

Configuration software.

1.4.6 EMI/RFI Compatibility

§ CE Compliant

1.4.7 Outputs

§ Visual – Fast Flash, Slow Flash, Steady ON, Intermittent Fast Flash
§ Audible – Dual, Selectable by Cabinet Module
§ Auxiliary Relays – Form C, Selectable Form A or B; Normally not

Energized or Normally Energized

§ Contact Rating – General Purpose: 1 Amps @ 28 Vdc; 0.65 Amp @

115 Vac

§ Common System Trouble – Form C, 2 Amps @ 28 Vdc; 0.65 Amp @

115 Vac – Open Collector Transistor Output 200 mA @ 28 Vac

§ Common System Reflash – Form C, 2 Amps @ 28 Vdc; 0.65 Amp @

115 Vac – Open Collector Transistor Output 200 mA @ 28 Vac

1.4.8 Controls

§ Momentary Push Button: Integral or Remote; Single Pole
§ Normally Open; +V Switched; Silence; Acknowledge; Reset, Test,

GP1, GP2

1.4.9 Diagnostic

§ System Trouble Alarm (RUN) – Form C, 2 Amps @ 28 Vdc; 0.65

Amp @ 115 Vac

§ System Trouble Alarm (RUN) – Indicating LED Green
§ Communication Diagnostic (ERROR) – Indicating LED Red
§ Transmit/Receiver LED Pair

Advertising