Rev 1.0 Series X11CA Hardware Manual

3. Event Sequences

Hardware Control-© 2002 Ronan Engineering

37

3.4.7 F3M-1

First out manual reset.

The first out alarm in a group is distinguished by unique display until the first out
function is reset. Because Acknowledge is not used to reset the first out function,
the new first alarm and subsequent alarms can be acknowledged so that the new
alarms can be distinguished from the previously acknowledged alarms. The
subsequent alarms return to normal state only if they are in the normal state when
the Reset is operated and the first out group has been reset.