5. Explanation of Operating Functions

53

5.3.2 Timings after Power On

Follow the procedure below to turn on the power after confirming that the slider or rod is not contacting a

mechanical end nor the load is contacting any peripheral equipment:

[1] Cancel the emergency stop or turn on the motor drive power.

[2] Supply the 24-VDC controller power.

If 24 VDC is supplied in a condition where no emergency stop is actuated, the servo will be turned on

automatically in the controller.

[3] Initial setting of minimum parameter(s) required

(Example) x To change the feed speed during teaching:

Change parameter No. 35 (Safety speed).

[4] Using a PC or teaching pendant to set optimal values in the “Position,” “Speed,” “Acceleration” and

“Deceleration” fields, etc., of the position table.

Caution: When the power is turned on while an emergency stop is actuated, and then the emergency

stop is cancelled, the servo will turn on with a maximum delay of 170 msec after the

cancellation of emergency stop.

Safety circuit condition

Supply of 24-VDC

controller power

SV lamp

(on front panel)

Controller ready

(PWR)

Pause (STP)

Servo ON command

(SON)

Servo ready (SV)

Position complete

(PEND)

Emergency stop cancelled

Orange light illuminates for 2 seconds, and

then turns off.

Green

Initial parameter

Initial condition “1”

Pause cancelled

170 msec max.

Emergency stop cancelled

170 msec max.

Servo on