10. Connection with Controller

x When fixing the cable, provide a moderate slack and do not tension it too tight.

x Separate the I/O and communication lines from the power and drive lines.

Do not wire them together in the same duct.

x Pay attention to the following points when using a cable track.

x Do not let the cable get tangled or kinked in a cable track or flexible tube. When bundling the cable,

keep a certain degree of flexibility (so that the cable will not become too taut when bent).

x Do not cause the cables to occupy more than 60% of the space in the cable track.

Warning

z Always turn off the controller power before connecting/disconnecting cables. If cables are

connected/disconnected while the power is still supplied, the actuator may malfunction and a serious
injury or equipment damage may occur.

z Loose connectors may cause the actuator to malfunction and create a dangerous situation. Be sure

to confirm that all connectors are securely connected.

Do not use a spiral
tube where the cable
flexes frequently.

Power line

I/O lines
(flat cable)

Duct

Cable

Cable track