1.6 Installation and Noise Elimination

(1) Noise Elimination Grounding (Frame Ground)

Connect it using an earth cable
made of soft copper with the diameter
of AWG16 (1.25mm

2

).

Class D grounding

(Formerly Class-III grounding: Grounding resistance at 100

 or less)

Controller

Controller

Other

equipment

Other

equipment

Other

equipment

Do not share the ground wire with or connect
to other equipment. Ground each controller.

(2) Precautions regarding wiring method

1) Twist the wires for the 24V DC power unit.

2) Separate signal lines and encoder cables from

high-power lines such as the power wire.

(3) Noise Sources and Elimination

Carry out noise elimination measures for power devices on

the same power path and in the same equipment.

The following are examples of measures to eliminate noise

sources.

1) AC solenoid valves, magnet switches and relays

[Measure]

Attach the surge killer in parallel with the

coil.

2) DC solenoid valves, magnet switches and relays

[Measure]

Attach the diode in parallel with the coil.

For the DC relay, use the built-in diode type.

Noise Killer

+24V

+24V

0V

0V

Relay
coil

Relay coil

R

C

+

-