KB Electronics KBAC-48 User Manual

Page 19

Advertising
background image

19

6.4.2 Setting the Drive for Two Times

the Rated Motor RPM – The drive

can also be used to operate

the motor up to two times the

rated RPM. However, constant

horsepower will result when

operating the drive in the “2X”

mode above the motor rated

frequency. See Figure 21.

For 120 Hz output with 60 Hz

motor, set Jumper J4 to the “2X”

position and be sure Jumper J5

is set to the “60Hz” position. For

100 Hz output with 50 Hz motor,

set Jumper J4 to the “2X” position

and set Jumper J5 to the “50Hz”

position. See Figure 22.

6.5 Boost Mode Selection (J6) – Jumper

J6 is factory set to the “FIX” position for

Fixed Boost. For Adjustable Boost using

the BOOST Trimpot, set Jumper J6 to the

“ADJ” position. See Figure 23 on page 20.

Also see Section 13.8 on page 26 for

the BOOST Trimpot range.

6.6 Braking Mode Selection (J7) –

Jumper J7 is factory set to the “RG”

position for Regenerative Braking when

the Start/Stop Switch is set to the “STOP”

position. For DC Injection Braking, set

Jumper J7 to the “INJ” position. See

Figure 24 on page 20. Also see Section 13.5

on page 24.

When the Injection Brake Mode is

selected, the DECEL Trimpot is used to

adjust the brake time and intensity.

6.7 Run/Fault Output Relay Operation

Selection (J8) – Jumper J8 is factory

set to the “R” position for “Run” operation

of the Run/Fault Relay. For “Fault”

operation of the Run/Fault Relay, set

Jumper J8 to the “F” position.

See Figure 25 on page 20.

For Run/Fault Relay output contacts,

see Section 5.8 on page 17. The Run/Fault

Relay contact status for various drive

operating conditions is shown in Table 6

on page 17.

6.8 Stop Contact Selection (J9) – Jumper

J9 is factory set to the “NO” position for a

normally open stop contact. For remote

normally closed stop contact, set Jumper

J9 to the “NC” position. See Figure 26 on

page 20. For wiring information, see

Section 5.5 on page 16.

Automatic Ride-Through

(Factory Setting)

(J3 Installed in “A” Position)

Manual Start

(J3 Installed in “M” Position)

A

J3

M

A

J3

M

Figure 19 – Automatic Ride-Through

or Manual Start Selection*

*On Model KBAC-24D, Jumper J3 is labeled “AUTO” and “MAN”.

60 Hz Motor Operation

(Factory Setting)

(J4 Installed in “1X” Position)

(J5 Installed in “60Hz” Position)

50 Hz Motor Operation

(J4 Installed in “1X” Position)

(J5 Installed in “50Hz” Position)

50H

z

J5

60H

z

2X

J4

1X

50H

z

J5

60H

z

2X

J4

1X

Figure 20 – 60 Hz & 50 Hz Motor Selection

50/60

Output Frequency (Hz)

0

2

0

% T

orque 50

100/120

100

Figure 21 – Available Torque vs. Output Frequency

120 Hz Output with 60 Hz Motor

(J4 Installed in “2X” Position)

(J5 Installed in “60Hz” Position)

100 Hz Output with 50 Hz Motor

(J4 Installed in “2X” Position)

(J5 Installed in “50Hz” Position)

50H

z

J5

60H

z

2X

J4

1X

50H

z

J5

60H

z

2X

J4

1X

Figure 22

120 Hz & 100 Hz Drive Output Frequency Selection