Vanguard CT-3500 User Manual

Page 16

Advertising
background image

Model CT-3500

Operating Procedures

12

Figure 6.0

A typical CT-3500 CLOSE-OPEN Test print out

Note:

If the timing shot was a dual operation (e.g.,
CLOSE-OPEN), the display will display the
test results first operation (in this case
CLOSE) then the second operation (OPEN)
and finally time between the two operation
(contact LIVE time).

A typical CLOSE-OPEN operation the first
test results (CLOSE) is shown as follows:

a. Press ENTER key to advance to the next
display (i.e., second-stroke bounce time).

b. Press ENTER key to advance to the next
display (i.e., second-stroke bounce time).

OPEN (mS / CYCLES)
A 1632.80mS 97.96CY
B 1628.50mS 87.71CY
C 1631.70mS 97.90CY

CLOSE (mS / CYCLEs)
A 171.80mS 10.30CY
B 174.20mS 10.45CY
C 172.00mS 10.32CY

CLOSE BOUNCE TIME
A 32.10mS 1.92CY
B 00.90mS 0.05CY
C 14.80mS 0.88CY