Vanguard CT-3500 User Manual

Page 21

Advertising
background image

Model CT-3500

Operating Procedures

17

Use the following steps to set 50/60Hz
mode:
a. Beginning at the START-UP MENU,
press key #2 (SETUP) to display the SET-
UP MENU shown below:

SET-UP MENU

b. Press key #4 (NEXT PAGE) to display
the menu shown below:

c. Press key #3 (SET 50/60 Hz) to select
the Menu for power-line frequency that the
breaker controls. This displays the Set Line
Frequency menu shown below:

d. Press the key for the frequency of power
that the breaker controls when it’s in service
(i.e., on line). When either the #1 or #2 key
is pressed, the display returns to the Start-Up
Menu.
This ends the Set Line Frequency procedure.

5.12

Cable Test Procedure

The purpose of the Cable Test is to quickly
check the test leads and breaker contacts for
continuity at each of the 3 phase contacts.
(For example, a close test should begin with
all contacts open; conversely an open test
should begin with all three contacts closed—
the closed condition also checks continuity
of the test leads for opens or erroneous

hookups.) When the test hookup is made to
the breaker, run a Cable Test to make sure
all 3 test lead clips are properly connected
(contact clips are across mating contacts).
Begin with the Start-Up Menu (below):

START-UP MENU

a. After test hookup to the breaker, open
the breaker and press key #3 (Cable Test).
The display below shows the line status of
each of three sets of contacts (all three
should show open).

b. Press ENTER key to return to Start-Up
Menu.

c.

Set the breaker contacts to the closed

condition and again press key #3 (cable test)
on the Start-Up Menu. The display below
shows the line status of each of three sets of
contacts (all three should show close).

d. Press ENTER to return to Start-Up
Menu.

This completes the Cable test procedure.

This completes all operating procedures

1. ENTER ID
2. REVIEW SHOT
3. RESTORE SHOT
4. NEXT PAGE

1. COMPUTER CONTROL
2. SET TIME
3. SET 50/60 Hz

SET LINE FREQUENCY
1. 60 Hz
2. 50 Hz

1. RUN TEST 05/15/01
2. SETUP 10:28:03
3. CABLE TEST

CABLE TEST

CH A CH B CH C
OPEN OPEN OPEN

(ANY KEY TO EXIT)

CABLE TEST

CH A CH B CH C
CLOSE CLOSE CLOSE

(ANY KEY TO EXIT)

Advertising